7 editable documents: the full Water Management
Plan built to the seven ASHRAE 188-2021 §6.2 elements, the monitoring
and sampling log set, corrective-action forms, an annual-review
checklist, and the New Jersey S2188 and New York City LL159 supplement
sheets — each mapped to the exact section it satisfies, with a stated
retention period and a plain-English fill-in guide.
Retention: Keep the current WMP on the building premises for immediate inspection; in New Jersey retain the WMP and all implementation records at least 5 years (N.J.S.A. 26:1A-140 §6.f.2). Update on any material system change and review at least annually.
Regulation / standard this document satisfies:
ANSI/ASHRAE — ANSI/ASHRAE Standard 188-2021, §6 (esp. §6.2)
General Requirements — §6.2 sets the seven required Water Management Program elements: (1) program team, (2) description of building water systems with process flow diagrams (§6.2.2), (3) hazard analysis / control locations, (4) control measures with control limits, (5) monitoring, (6) corrective/management response, (7) verification and validation; §6.2.8 covers the Legionella-testing decision.
ASHRAE 188-2021 is copyrighted; the pack maps each template section to the standard's element structure and cites it, but does not reproduce the standard's normative text. Buyers must hold a licensed copy of the standard. Purchase/preview: https://www.ashrae.org/technical-resources/bookstore/ansi-ashrae-standard-188-2021-legionellosis-risk-management-for-building-water-systems. The 2021 edition replaced permissive with enforceable language.
Requirements for Building Water Systems — potable and nonpotable system-specific requirements (operating manuals §7.3.6, water features §7.4, etc.) that the plan's control measures and monitoring must cover.
ANSI/ASHRAE — ANSI/ASHRAE Standard 188-2021, Normative Appendix A
Health Care Facilities — additional normative water-management requirements for hospitals and other health-care buildings (the 2021 edition renamed the 2018 'Annex A' to 'Appendix A').
Infection-control Conditions of Participation — the enforceable basis CMS reads as requiring a Legionella water management program: §482.42 (hospitals — sanitary environment + active infection-control program), §483.80 (LTC — infection prevention & control program), and §485.635(a)(3)(vi) (critical access hospitals — system to identify, report, investigate, and control infections).
This is the standing enforceable authority for CMS-certified facilities regardless of the QSO memo's expiry. §483.80 is at https://www.ecfr.gov/current/title-42/section-483.80 and §485.635 at https://www.ecfr.gov/current/title-42/section-485.635 .
Retention: Retain monitoring, temperature, disinfectant, flushing, and cooling-tower Legionella sampling records at least 5 years in NJ (§6.f.2); NYC cooling-tower records must be producible on demand and retained per 24 RCNY Ch. 8.
Regulation / standard this document satisfies:
ANSI/ASHRAE — ANSI/ASHRAE Standard 188-2021, §6 (esp. §6.2)
General Requirements — §6.2 sets the seven required Water Management Program elements: (1) program team, (2) description of building water systems with process flow diagrams (§6.2.2), (3) hazard analysis / control locations, (4) control measures with control limits, (5) monitoring, (6) corrective/management response, (7) verification and validation; §6.2.8 covers the Legionella-testing decision.
ASHRAE 188-2021 is copyrighted; the pack maps each template section to the standard's element structure and cites it, but does not reproduce the standard's normative text. Buyers must hold a licensed copy of the standard. Purchase/preview: https://www.ashrae.org/technical-resources/bookstore/ansi-ashrae-standard-188-2021-legionellosis-risk-management-for-building-water-systems. The 2021 edition replaced permissive with enforceable language.
Requirements for Building Water Systems — potable and nonpotable system-specific requirements (operating manuals §7.3.6, water features §7.4, etc.) that the plan's control measures and monitoring must cover.
New York City (DOHMH) — NYC Local Law 159 of 2025; 24 RCNY Chapter 8 (cooling towers)
New York City cooling-tower Legionella rule — as of 2026-05-07, Legionella culture testing must be performed on every cooling-tower system at least once every 31 days during the operating season (replacing the 90-day interval under LL77); each test date must be reported to DOHMH within 5 days; culture analyses must use a NYS ELAP-certified lab; a Maintenance Program & Plan (MPP) must be kept on site and certified annually. LL159 adds to, and does not replace, Local Law 77 of 2015.
Conforming amendments to 24 RCNY Chapter 8 took effect 2026-05-08. Enhanced summer disinfection Jul 1-Aug 31; a cooling tower is 'in operation' once filled/partially filled; failure to produce records on request is prima facie evidence the requirement was not met; penalties increased (most doubled), starting at $10,000/violation.
Retention: Retain each corrective-action / management-response record with the WMP; at least 5 years in NJ (§6.f.2).
Regulation / standard this document satisfies:
ANSI/ASHRAE — ANSI/ASHRAE Standard 188-2021, §6 (esp. §6.2)
General Requirements — §6.2 sets the seven required Water Management Program elements: (1) program team, (2) description of building water systems with process flow diagrams (§6.2.2), (3) hazard analysis / control locations, (4) control measures with control limits, (5) monitoring, (6) corrective/management response, (7) verification and validation; §6.2.8 covers the Legionella-testing decision.
ASHRAE 188-2021 is copyrighted; the pack maps each template section to the standard's element structure and cites it, but does not reproduce the standard's normative text. Buyers must hold a licensed copy of the standard. Purchase/preview: https://www.ashrae.org/technical-resources/bookstore/ansi-ashrae-standard-188-2021-legionellosis-risk-management-for-building-water-systems. The 2021 edition replaced permissive with enforceable language.
Retention: Retain each completed annual review with the WMP; at least 5 years in NJ (§6.f.2).
Regulation / standard this document satisfies:
ANSI/ASHRAE — ANSI/ASHRAE Standard 188-2021, §6 (esp. §6.2)
General Requirements — §6.2 sets the seven required Water Management Program elements: (1) program team, (2) description of building water systems with process flow diagrams (§6.2.2), (3) hazard analysis / control locations, (4) control measures with control limits, (5) monitoring, (6) corrective/management response, (7) verification and validation; §6.2.8 covers the Legionella-testing decision.
ASHRAE 188-2021 is copyrighted; the pack maps each template section to the standard's element structure and cites it, but does not reproduce the standard's normative text. Buyers must hold a licensed copy of the standard. Purchase/preview: https://www.ashrae.org/technical-resources/bookstore/ansi-ashrae-standard-188-2021-legionellosis-risk-management-for-building-water-systems. The 2021 edition replaced permissive with enforceable language.
Infection-control Conditions of Participation — the enforceable basis CMS reads as requiring a Legionella water management program: §482.42 (hospitals — sanitary environment + active infection-control program), §483.80 (LTC — infection prevention & control program), and §485.635(a)(3)(vi) (critical access hospitals — system to identify, report, investigate, and control infections).
This is the standing enforceable authority for CMS-certified facilities regardless of the QSO memo's expiry. §483.80 is at https://www.ecfr.gov/current/title-42/section-483.80 and §485.635 at https://www.ecfr.gov/current/title-42/section-485.635 .
Retention: Retain the WMP and all procedure, testing, and implementation records on premises at least 5 years (N.J.S.A. 26:1A-140 §6.f.2).
Regulation / standard this document satisfies:
State of New Jersey — N.J.S.A. 26:1A-140 (P.L.2024, c.66 / S2188), §6
New Jersey Legionnaires' disease law — owners/operators of covered buildings must DEVELOP a water management program consistent with ASHRAE 188-2018 (or subsequent versions) within 24 months of the 2024-09-12 effective date (= 2026-09-12, §6.a) and IMPLEMENT it within 27 months (= 2026-12-12, §6.f.1); post a public notice on the premises (§6.c); retain the WMP, all procedure/testing records, and implementation documentation on premises at least 5 years (§6.f.2); civil penalties $2,000 / $5,000 / $10,000 (§6.g).
Codified N.J.S.A. 26:1A-139 to 142 + 58:12A-12.10 to 12.13. Eight covered criteria (§6.a(1)-(8)): hospitals; nursing/assisted-living/residential care/dementia homes; buildings with whirlpool/spa/pool/cooling tower/fountain/mister/humidifier; correctional facilities with centralized hot water; residential high-rises (6+ floors) with centralized water heaters; hotels/motels (25+ units, centralized hot water); subsidized/senior residential (25+ units); and any building DOH ties to an outbreak. Excludes residential properties of 4 or fewer dwelling units.
ANSI/ASHRAE — ANSI/ASHRAE Standard 188-2021, §6 (esp. §6.2)
General Requirements — §6.2 sets the seven required Water Management Program elements: (1) program team, (2) description of building water systems with process flow diagrams (§6.2.2), (3) hazard analysis / control locations, (4) control measures with control limits, (5) monitoring, (6) corrective/management response, (7) verification and validation; §6.2.8 covers the Legionella-testing decision.
ASHRAE 188-2021 is copyrighted; the pack maps each template section to the standard's element structure and cites it, but does not reproduce the standard's normative text. Buyers must hold a licensed copy of the standard. Purchase/preview: https://www.ashrae.org/technical-resources/bookstore/ansi-ashrae-standard-188-2021-legionellosis-risk-management-for-building-water-systems. The 2021 edition replaced permissive with enforceable language.
6. New York City LL159 / LL77 Cooling-Tower Supplement
Source file:nyc-supplement.md
Retention: Maintain the Cooling Tower Maintenance Program & Plan on site, certified annually; keep testing/inspection records producible on demand per 24 RCNY Chapter 8.
Regulation / standard this document satisfies:
New York City (DOHMH) — NYC Local Law 159 of 2025; 24 RCNY Chapter 8 (cooling towers)
New York City cooling-tower Legionella rule — as of 2026-05-07, Legionella culture testing must be performed on every cooling-tower system at least once every 31 days during the operating season (replacing the 90-day interval under LL77); each test date must be reported to DOHMH within 5 days; culture analyses must use a NYS ELAP-certified lab; a Maintenance Program & Plan (MPP) must be kept on site and certified annually. LL159 adds to, and does not replace, Local Law 77 of 2015.
Conforming amendments to 24 RCNY Chapter 8 took effect 2026-05-08. Enhanced summer disinfection Jul 1-Aug 31; a cooling tower is 'in operation' once filled/partially filled; failure to produce records on request is prima facie evidence the requirement was not met; penalties increased (most doubled), starting at $10,000/violation.
Retention: Reference document; retain the current adopted standard/rule versions and in-use templates for the life of the program. All underlying records: at least 5 years in NJ (§6.f.2).
Regulation / standard this document satisfies:
ANSI/ASHRAE — ANSI/ASHRAE Standard 188-2021, §6 (esp. §6.2)
General Requirements — §6.2 sets the seven required Water Management Program elements: (1) program team, (2) description of building water systems with process flow diagrams (§6.2.2), (3) hazard analysis / control locations, (4) control measures with control limits, (5) monitoring, (6) corrective/management response, (7) verification and validation; §6.2.8 covers the Legionella-testing decision.
ASHRAE 188-2021 is copyrighted; the pack maps each template section to the standard's element structure and cites it, but does not reproduce the standard's normative text. Buyers must hold a licensed copy of the standard. Purchase/preview: https://www.ashrae.org/technical-resources/bookstore/ansi-ashrae-standard-188-2021-legionellosis-risk-management-for-building-water-systems. The 2021 edition replaced permissive with enforceable language.
Historical surveyor guidance requiring Medicare/Medicaid hospitals, critical access hospitals, and long-term care facilities to develop and implement a Legionella water management program considering ASHRAE 188 and the CDC toolkit. CMS marked this memo EXPIRED on 2025-09-02; the enforceable basis now runs directly through the infection-control Conditions of Participation it cited.
[VERIFY] QSO-17-30 is EXPIRED as of 2025-09-02. Confirm the current replacement guidance number before citing QSO-17-30 as live in marketing copy. The underlying mandate is unchanged and enforceable via the CoPs (see cms-cop citation). Logged to DECISIONS-NEEDED.md.
Infection-control Conditions of Participation — the enforceable basis CMS reads as requiring a Legionella water management program: §482.42 (hospitals — sanitary environment + active infection-control program), §483.80 (LTC — infection prevention & control program), and §485.635(a)(3)(vi) (critical access hospitals — system to identify, report, investigate, and control infections).
This is the standing enforceable authority for CMS-certified facilities regardless of the QSO memo's expiry. §483.80 is at https://www.ecfr.gov/current/title-42/section-483.80 and §485.635 at https://www.ecfr.gov/current/title-42/section-485.635 .
State of New Jersey — N.J.S.A. 26:1A-140 (P.L.2024, c.66 / S2188), §6
New Jersey Legionnaires' disease law — owners/operators of covered buildings must DEVELOP a water management program consistent with ASHRAE 188-2018 (or subsequent versions) within 24 months of the 2024-09-12 effective date (= 2026-09-12, §6.a) and IMPLEMENT it within 27 months (= 2026-12-12, §6.f.1); post a public notice on the premises (§6.c); retain the WMP, all procedure/testing records, and implementation documentation on premises at least 5 years (§6.f.2); civil penalties $2,000 / $5,000 / $10,000 (§6.g).
Codified N.J.S.A. 26:1A-139 to 142 + 58:12A-12.10 to 12.13. Eight covered criteria (§6.a(1)-(8)): hospitals; nursing/assisted-living/residential care/dementia homes; buildings with whirlpool/spa/pool/cooling tower/fountain/mister/humidifier; correctional facilities with centralized hot water; residential high-rises (6+ floors) with centralized water heaters; hotels/motels (25+ units, centralized hot water); subsidized/senior residential (25+ units); and any building DOH ties to an outbreak. Excludes residential properties of 4 or fewer dwelling units.
New York City (DOHMH) — NYC Local Law 159 of 2025; 24 RCNY Chapter 8 (cooling towers)
New York City cooling-tower Legionella rule — as of 2026-05-07, Legionella culture testing must be performed on every cooling-tower system at least once every 31 days during the operating season (replacing the 90-day interval under LL77); each test date must be reported to DOHMH within 5 days; culture analyses must use a NYS ELAP-certified lab; a Maintenance Program & Plan (MPP) must be kept on site and certified annually. LL159 adds to, and does not replace, Local Law 77 of 2015.
Conforming amendments to 24 RCNY Chapter 8 took effect 2026-05-08. Enhanced summer disinfection Jul 1-Aug 31; a cooling tower is 'in operation' once filled/partially filled; failure to produce records on request is prima facie evidence the requirement was not met; penalties increased (most doubled), starting at $10,000/violation.
Every building-specific value is a merge field. Fill each one once and
it flows through the pack. Required fields must be completed before a
document is inspection-ready.
Merge fields — required
Field
Token
Example
Building owner / operator legal name
{{company_name}}
Riverside Senior Living LLC
Building / facility name
{{building_name}}
Riverside Tower A
Building street address
{{facility_address}}
500 Riverside Dr, Newark, NJ 07104
State / city jurisdiction (drives supplement)
{{jurisdiction}}
New Jersey
Water management program team leader (name / title)
{{program_manager}}
Pat Nguyen, Director of Facilities
Program team members + roles
{{team_members}}
J. Rivera (Engineering), M. Cole (Water Treatment Vendor)
Plan effective / adoption date
{{effective_date}}
2026-08-01
Prepared by (name / title / credential)
{{prepared_by}}
Pat Nguyen, CWT
Reviewed / validated by (name / credential)
{{reviewed_by}}
Dr. L. Foster, PE
Merge fields — optional / per-record
Field
Token
Example
Water treatment contractor / lab
{{water_treatment_vendor}}
AquaSafe Treatment Co. (ELAP #12345)
Cooling tower ID(s) (NYC registration no.)
{{cooling_tower_ids}}
CT-2026-0042
Next scheduled annual review date
{{review_date}}
2027-08-01
Get the pack
One-time purchase. Editable DOCX + print-ready PDF + implementation
guide, delivered as a single download.
ASHRAE 188 Water Management Plan Pack
A complete, editable Water Management Plan built to the seven required elements of ANSI/ASHRAE 188-2021 (§6.2), plus the monitoring logs, corrective-action forms, annual-review checklist, and NJ S2188 + NYC LL159 supplements — mapped section-by-section to the standard.
$399 one-time
vs $2,995/yr HC Info LAMPS subscription / generic free CDC PDF for the incumbent
Water Management Plan template — all 7 ASHRAE 188-2021 §6.2 elements
Program team roster + roles/responsibilities (§6.2.1)
System description + process flow diagram worksheets (§6.2.2)
Checkout was cancelled — no charge was made. You can try again above.
Checkout opens soon
Leave your email and we’ll notify you the day it goes live. No
card, no commitment, and we will not use your address for anything